BS RS 9P ( DB-9 ) SURGE PROTECTOR
BS RS 9P
Product Description:
For use at LPZ 2-3 boundary. The series of BS...P provide
surge protection for RS 485, RS 422 or RS 232 signal devices from
damage, such as surge voltage, operating over voltage, electrostatic
discharging and so on.
Main character:
※ High discharge capacity, low voltage protection, quick response
※ Does not impact the normal work of data management devices and system
※ Apply for high speed transmission devices
※ Core components are from international well known supplier
Parameters:
Type
|
BS RS 9P
|
|
Order No.
|
640 019
|
|
Nominal voltage
|
UN
|
12V-
|
Rated voltage
(max. Continuous voltage)
|
Uc
|
15V-
|
Nominal (8/20)
discharge current (10/1000)
|
In
|
100A(L/SG,SG/PG)
20A(L/SG,SG/PG)
|
Max. discharge current (8/20)
|
Imax
|
200A(L/SG,SG/PG)
|
Voltage protection
level at In
|
Up
|
≤24V(L/SG)
≤200V(SG/PG)
|
Voltage protection
level at 1kV/µs
|
Up
|
≤21V(L/SG)
≤90V(SG/PG)
|
Response time
|
tA
|
≤1ns
|
Max. data transmission rates
|
VS
|
1MBit/s
|
Operating temperature range
|
θ
|
-40℃…+80℃
|
Protective lines
|
Line:8/SG/PG
|
|
Pinning
|
Line:1/2/3/4/6/7/8/9,SG:5 Standby lines disconnected
|
|
Connection Input
Output
|
D-Sub plug/socket, 9 pins
|
|
Earthing via
|
Outgoing earth line 1.5mm2, long: 300mm
|
|
Installation
|
Connection line, pluggable
|
|
Enclosure material
|
Plastic, metallised
|
|
Test standards
|
YD/T 1542-2006;GB 18802.21-2004;IEC 61643-21:2000
|
|
Certification
|
CE (LVD,EMC)
|